Notice of Public Comment Period - Draft Air Quality Permit 7443 - CBNA Halmar Clean Rivers JV

PUBLIC NOTICE

Draft Air Quality Permit 7443, CBNA Halmar Clean Rivers JV, Operation of a 194 kWe diesel-fired non-emergency generator set at the Potomac River Tunnel project, CSO 022 site, 2800 Virginia Avenue NW, Washington DC

Notice is hereby given that, pursuant to 20 DCMR ยง 210, the Air Quality Division (AQD) of the Department of Energy and Environment (DDOE), located at 1200 First Street NE, 5th Floor, Washington DC, is proposing to issue an air quality permit (No. 7443) to CBNA Halmar Clean Rivers JV, to construct and operate one 194 kWe MQ Power diesel-fired non-emergency generator set, model DCA220SSJU4F3 and powered by a 323 bhp (241 kWm) John Deere engine with serial number 8011521at the Potomac River Tunnel project, CSO 022 site, 2800 Virginia Avenue NW, Washington DC. The contact person for the facility is Raoul Fernandez, Project Manager at [email protected] or by telephone (401) 919-8547.

The proposed emission limits are as follows:

a. Emissions from this generator shall not exceed those in the following table as tested pursuant to the applicable test methods in 40 CFR 1039, Subpart F [40 CFR 60.4200(a)(1)(i), 40 CFR 60.4200(a)(2)(i), 40 CFR 60.4201(a), 40 CFR 60.4204(b), 40 CFR 1039.101(a), (b), and (e)]:

Pollutant Emission Limits (g/kW-hr)

Emission Standard Type

NOx

CO

NMHC

PM

Transient and Steady State

0.40

3.5

0.19

0.02

Not-to-Exceed

0.60

4.4

0.29

0.03

b. Visible emissions shall not be emitted into the outdoor atmosphere from the engine, except that discharges shall be permitted for two (2) minutes during any start-up, cleaning, adjustment of combustion or operational controls, or regeneration of emissions control equipment; provided, that such discharges shall not exceed twenty-seven percent (27%) opacity (unaveraged). [20 DCMR 606.1 and 606.2(d)]

c. An emission into the atmosphere of odorous or other air pollutants from any source in any quantity and of any characteristic, and duration which is, or is likely to be injurious to the public health or welfare, or which interferes with the reasonable enjoyment of life or property is prohibited. [20 DCMR 903.1]

Violation of the requirements of this condition that occur as a result of unavoidable malfunction, despite the conscientious employment of control practices, shall be an affirmative defense for which the owner or operator shall bear the burden of proof. A malfunction shall not be considered unavoidable if the owner or operator could have taken, but did not take, appropriate steps to eliminate the malfunction within a reasonable time, as determined by the Department. [20 DCMR 903.13(b)]

This condition is District enforceable only.

d. The Permittee shall comply with the requirements for crankcase emissions, adjustable parameters, prohibited controls, and defeat devices specified in 40 CFR 1039.115. [40 CFR 60.4201(a), 40 CFR 60.4204(b)]

Estimated Maximum Potential Emissions:

The following table shows estimated maximum potential emissions from the generator set, based on continuous operations (24 hours per day, 365 days per year) and certified engine emissions listed on the manufacturer's exhaust emissions data sheet (except oxides of sulfur, which is based on EPA's AP-42 emission factor).

Pollutant Potential Emissions (tons per year)
Total Particulate Matter (PM Total)

0.04

Oxides of Sulfur (SOx)

2.90

Oxides of Nitrogen (NOx)

0.14

Volatile Organic Compounds (VOC)

0.04

Carbon Monoxide (CO)

0.02

The permit application and supporting documentation, along with the draft permit are available for public inspection at AQD and copies may be made available between the hours of 9:00 A.M. and 5:00 P.M. Monday through Friday. Interested parties wishing to view these documents should provide their names, addresses, telephone numbers and affiliation, if any, to Stephen S. Ours at (202) 498-8143 or [email protected]. Copies of the draft permit and related technical support memorandum are also available in the attachments section below.

Interested persons may submit written comments or may request a hearing on this subject within 30 days of publication of this notice. The written comments must also include the person's name, telephone number, affiliation, if any, mailing address and a statement outlining the air quality issues in dispute and any facts underscoring those air quality issues. All relevant comments will be considered before taking final action on the permit application.

Comments on the proposed permit and any request for a public hearing should be addressed to:

Stephen S. Ours
Chief, Permitting Branch - Air Quality Division

Department of Energy and Environment

1200 First Street NE, 5th Floor
Washington DC 20002

[email protected]

No comments or hearing requests submitted after December 7, 2026 will be accepted.

For more information, please contact Stephen S. Ours at (202) 498-8143 or [email protected].

District of Columbia Department of the Environment published this content on November 06, 2026, and is solely responsible for the information contained herein. Distributed via Public Technologies (PUBT), unedited and unaltered, on November 06, 2026 at 22:38 UTC. If you believe the information included in the content is inaccurate or outdated and requires editing or removal, please contact us at [email protected]